Heat pumps are rated by AHRI for heat output at two outdoor temperatures, 47°F and 17°F. The indoor return air temperature rating point is 70°F. Most heat pumps produce a heat output of close to their "tonnage rating" at the 47°F AHRI rating point and approximately half of their "tonnage rating" at 17°F. Most units operate correctly with an airflow somewhere in the range of 400 CFM per ton of capacity. Of course these are generalizations.
However, a general idea of temperature rise parameters can prove useful. Using these generalized assumptions, let's develop some generalized temperature rise performance parameters. The basic formula to use is BTU = 1.08 x CFM x TEMP RISE. This can be rewritten as TEMP RISE = BTU / (1.08 x CFM). At 47°F the capacity per ton will be 12,000 BTU. Plugging this into the formula we get TEMP RISE = 12,000 / (1.08 x 400). This yields a projected temperature rise of 28°F at a 47°F ambient. On the other end of things, the assumed capacity per ton at 17°F ambient temperature is 6000 BTU. Plugging this in we get TEMP RISE = 6000 / (1.08 x 400). This yields a projected temperature rise of 14°F. You can readily see that the result of a 50% reduction in capacity yields a 50% reduction in temperature rise. Now let's test our mathematical extrapolations against some REAL data taken from a manufacturer’s performance specifications.
Model
|
ΔT @ 47°F
|
ΔT @ 17°F
|
BTUh @ 47°F
|
BTUh @ 17°F
|
CFM
|
ERHQ18
|
26°F
|
13°F
|
18,500
|
11,000
|
700
|
ERHQ24
|
25°F
|
12°F
|
24,400
|
12,500
|
800
|
ERHQ30
|
27°F
|
16°F
|
32,200
|
18,800
|
1055
|
ERHQ36
|
26°F
|
13°F
|
36,000
|
19,500
|
1310
|
The manufacturer states that a properly operating unit should be + or – 3°F of these typical values. You will note that our extrapolated values are all within the 3°F margin of error.
But what if the temperature is neither 47°F nor 17°F, what temperature rise do you look for then? Another assumption is in order here; we will assume that the capacity reduction due to ambient temperature drop is even. Since the temperature rise changed from 28°F to 14°F over a 30°F ambient change, this would represent approximately a 1°F change in temperature rise for every 2°F change in ambient temperature. In the above table, we see a temperature rise change of 13°F in 3 out of the 4 units listed. This gives similar results. In our assumed system, 28°F rise at 47°F ambient and a 14°F rise at 17°F ambient, a temperature rise of 23°F would be expected at 37°F ambient based on the relationship of 1°F rise per 2°F ambient temperature. Clearly, manufacturer's data for a specific unit is more accurate than extrapolated benchmarks; however, extrapolated temperature rise calculations are considerably more accurate than blocking the outdoor coil and pretending it's summer. Remember: the best method for charging any unit is the method recommended by the people who made it!
But what if the temperature is neither 47°F nor 17°F, what temperature rise do you look for then? Another assumption is in order here; we will assume that the capacity reduction due to ambient temperature drop is even. Since the temperature rise changed from 28°F to 14°F over a 30°F ambient change, this would represent approximately a 1°F change in temperature rise for every 2°F change in ambient temperature. In the above table, we see a temperature rise change of 13°F in 3 out of the 4 units listed. This gives similar results. In our assumed system, 28°F rise at 47°F ambient and a 14°F rise at 17°F ambient, a temperature rise of 23°F would be expected at 37°F ambient based on the relationship of 1°F rise per 2°F ambient temperature. Clearly, manufacturer's data for a specific unit is more accurate than extrapolated benchmarks; however, extrapolated temperature rise calculations are considerably more accurate than blocking the outdoor coil and pretending it's summer. Remember: the best method for charging any unit is the method recommended by the people who made it!