Condensate Drain Cleaning

It is time for annual spring AC maintenance calls. One thing you should be doing is cleaning out the condensate line and checking to see that the condensate drain is working properly. The customer is paying you for a seasonal maintenance to avoid having problems – such as a mess caused by something as simple as a clogged drain line. If you can get to the condensate drain easily, you can blow it out with nitrogen using a rubber stopper with a 1/4” copper pipe and flare connection.

Gallo Gun









Another option is the Gallo Gun that uses CO2 charges. Both of these options require access to the drain opening inside the evaporator drain pan. The drain opening is usually accessible on cased coils by removing a panel on the front of the coil casing. Likewise, the drain opening for the coil in most heat pump air handlers can be accessed by removing the front panels.


However, for coils in hard to reach places, or coils installed inside a plenum with no access panel, it may be easier to suck out the muck using a Sludge Sucker. The Sludge Sucker is installed on the drain outlet. Nitrogen pressure creates a vortex which makes a strong suction on the drain line, sucking out the water and muck in the entire drain system.
Uniweld Sludge Sucker


Foe some systems you may need to clean out the condensate line trap. If  the drain is already plugged, then chances are the trap is plugged. Most manufacturers require condensate line traps. The trap is designed to stop air from sucking in through the condensate line during operation. Unfortunately, because traps tend to trap stuff, they get blocked with crud. Most codes now require that condensate lines have clean-outs which allow the trap to be cleaned without cutting out the existing trap and replacing it. For many site built traps, this has been common for many years. The only practical way to clean them was actually to just replace them.

If you do have to cut out and replace a condensate trap, make sure that what you replace it with can be opened and cleaned. This can be done by installing tees in a couple of places where you would normally use ells and plugging or capping the unused branch. Alternatively, you can use a manufactured product such as the Rectorseal EZ Trap of the All-Access AA1 cleanout.
Rectorseal EZ Trap
All Access AA1
































Another solution would be to remove the traditional trap and replace it with a product designed to provide a drain seal without trapping water. Three types are available – the Cost Guard condensate drain seal by Trent Technologies, the Air Trap by Des Champs Technologies, and the Rectorseal Waterless Kit for their EZ Trap. I will talk more about how these work in a future post.
Trent Technologies Cost Guard

Des Champs Air Traps
Rectorseal Waterless Kit


If the system you are working on does not have a safety overflow switch installed, consider adding one. The safety switch is typically wired in series with “Y” to prevent the outdoor unit from operating and creating more water.  Some are installed in the primary drain clean-out, and some are installed in the secondary drain port. They are inexpensive, easy to add, and help prevent property damage. In the case of coils installed on top of furnaces, they can prevent the destruction of expensive electronic components inside the furnace from an overflowing condensate drain.
Rectorseal Safety Switch in primary drain

Diversitech safety switch in secondary drain


Saturday, September 13, 2014

Keep the Condensnot Moving!



The evaporator condensate drain is often one of the last things run when installing an air conditioner and sometimes is not given a lot of thought. The trouble is it can demand your attention if it does not work. A check list for constructing a working condensate drain that will continue to work and be easily maintained would be
1. The drain should have cleanouts near the unit and the trap to allow for routine maintenance.
2. Draw through coils should always have a trap after the drain pan.
3. The trap should be 4” deep and hold 2” of water.
4. The leaving side of the trap should be at least 2 inches lower than the drain pan outlet.
5. After leaving the trap, the condensate line should slope at least 1/8” per foot.
6. Except for the one trap at the unit, the condensate line should NEVER run up.
7. Long condensate lines may require a vent. If you install a vent, you MUST install a trap and the vent must be AFTER the trap, never before the trap.
8. In humid areas the parts of the condensate line closest to the unit may need to be insulated to prevent sweating.

Cleanout
Drains are getting a little more attention these days because the newer mechanical codes require cleanouts. In the past condensate drains were often cleaned by cutting out the old trap, blowing out the line, and installing a new trap. Now you are required to leave a way to access and clean the drain without cutting into it. Some people use tees or crosses at places where elbows would normally go. You can also purchase some fittings to install in the drain line that make accessing and cleaning the drain line easy. One is called “ALL-Access” Link http://www.allaccessdevice.com/
Another is offered by Rectorseal http://www.rectorseal.com/index.php/easy-klear/
Rectorseal also makes a manufactured trap which is clear, allowing you to see when the trap is full of “condensot.” It has service access built in as well. http://www.rectorseal.com/index.php/ez-trap/

Trap
A trap is always required with a draw through coil, otherwise, water will be held in by the negative pressure and the air flowing in through the drain. Many people don’t trap positive pressure coils, such as a coil installed on a furnace. Usually, they will drain because the pressure is pushing the water out. One argument for leaving the trap off on positive pressure coils is that traps tend to get clogged more quickly with “condensnot,” the slimy brown algae that grows in drain pans and drain lines. However, if the air velocity on a blow through coil is high enough, it may still have a negative pressure at the drain outlet. Adding a trap on a blow through coil also provides an air seal between the coil and the outside Manufacturers often specify traps even on blow through coils. Packaged units often specifically warn NOT to trap because they sometimes have a built in trap, and adding another would amount to double trapping. The trap needs to hold enough water to offset the negative pressure of the coil. A common specification calls for a 4” deep trap with a 2” riser so that the trap holds 2” of water and the outlet is 2 “ below the drain pan outlet.

Vent
Ever notice that plumbing systems have vents? The vent keeps the draining water and effluent from creating a suction which can slow or even stop drainage. On longer condensate lines, a vent may be required to insure drainage. Vents can also help on lines with minimal slope. The vent is just a tee with a riser which is open to the air. When used, there MUST be a trap and the vent should be AFTER the trap. Putting a vent before the trap pretty much undoes any good the trap would do by allowing air to pass through the vent. The vent should be at the start of the condensate line (but after the trap) and the riser should go above the rim of the drain pan.  

Slope
One of the laws of plumbing is that waste products run down hill. After the line leaves the trap at the unit it should never go back up. Running the line up after dropping down creates a second trap. Remember that the line is not under pressure, it is gravity flow. It is easy for “condensnot” to accumulate at this second trap and cause the drain to overflow at the unit. I am embarrassed to admit that I have personal knowledge of this. An unintended second trap is a messy service call waiting to happen.

Insulation
If your unit runs a lot and the coil is located in a humid area, the condensate line can sweat. Usually, the PVC is enough insulation to prevent this, but in some areas people have had problems with dripping condensate lines from sweating. Insulating the trap and all the drain between the trap and the unit with armaflex takes care of this.

Instructions
Finally, always follow the manufacturer’s instructions. They usually are pretty specific about how the drain is to be run. Trapped or not trapped, vented or not vented – those things are all typically in the instructions. Here is a link to another online posting that shows one manufacturer’s instructions and a drain run according to those instructions.