Sunday, April 9, 2017

How Much Refrigerant Does it Take to Make the Fan Blow Harder?

My brother Richard sometimes finds himself helping younger technicians who are stumped and need the help of an experienced professional technician. However, they have to really need help because they know Richard is going to twist their tail a bit in the process.

One day a frustrated tech called and told Richard that he was working on a system with a low suction pressure that was frosting up. He further explained that his new digital gauges were telling him that the superheat was 0, so he added refrigerant. However, no matter how much refrigerant he added, the superheat would not increase.

Richard asked him, “how much refrigerant do you have to add to make the fan blow harder?” There was no response, so Richard asked again, “Tell me, I really don’t know. How much refrigerant does it take to make the fan blow harder?” Finally, the tech responds: “Your question makes no sense! There is no relationship between the amount of refrigerant in the system and how hard the fan blows.” Richard then replies “So why are you trying to fix an airflow problem by adding refrigerant?”

While it is true that an undercharge can cause an air conditioning system to frost, the most common cause of a frosting air conditioning coil is actually low airflow. Always look at airflow issues first when trying to remedy a frosting air conditioning system. Common airflow issues include a dirty air filter, a dirty evaporator coil (caused by dirty air filters), closed registers, and poor ductwork.

One tip-off is superheat.  A system with airflow issues will operate with a low superheat while an undercharged system will operate with a high superheat. Note that if the coil is frozen over it will need to be defrosted before any pressures or temperatures are checked. The ice covering the coil makes its own airflow restriction.

Wednesday, April 5, 2017

PHCC Scholarship Deadline May 1

Could you use another $1000 to help with your HVACR Education? The Plumbing, Heating and Cooling Contractors (PHCC) are handing out money! Specifically, PHCC has announced that the deadline to apply for a PHCC Scholarship is May 1st. The PHCC has 41 different awards totaling $87,500 to give to deserving students. Each awrd ranges from $1000 - $5000.

Eligibility Requirements For All Applicants

  • A minimum cumulative grade point average of at least 2.0 for my previous academic work.
  • A citizen of the United States or Canada.
  • Have not previously won a scholarship from the Foundation. 

There are Scholarships for Apprentices, Technical School Students, and Students working towards a Bachelor's Degree

Apprentice Requirements

  • You are or will be enrolled in an Apprentice Program
  • You are or will be will be enrolled this year in a plumbing or HVACR apprentice program.
  • You also work full-time for a licensed plumbing or HVACR contractor who is a member of the Plumbing-Heating Cooling Contractors—National Association (PHCC).
  • Provide the PHCC Member Company Name, City & State:

Note: A max. of four employee scholarship applications per company will be accepted for consideration per year.

Community College and  Technical School Student Requirements
  • You are or will be enrolled in a Community College, Trade or Technical School
  • You are or will be enrolled this year in a full-time degree or certificate program at an accredited two-year community college, technical college or trade school.
  • You are or will be enrolled in an approved major directly related to the plumbing-heating-cooling profession.
  • Approved majors are: business management; construction management specializing in mechanical construction; HVACR installation, service or repair; mechanical CAD design; and plumbing installation, service or repair.*

Note: The PHCC of Massachusetts & PHCC of Texas Auxiliary scholarships have no restrictions on course of study.

Four Year College Student Requirements
You are or will be enrolled in a Four-Year College or University
You re or will be enrolled this year in a full-time undergraduate degree program at an accredited four-year college or university.
You  are or will be enrolled in or will be enrolling in an approved major directly related to the plumbing-heating-cooling profession.
Approved majors are: business management; construction management or science, specializing in mechanical construction; and mechanical engineering.*
Note: The PHCC of Massachusetts & PHCC of Texas Auxiliary scholarships have no restrictions on course of study.

Where to Apply

You can apply online here https://www.surveymonkey.com/r/PHCCScholarships
Or download and complete the pdf form found here
http://s3.amazonaws.com/rdcms-phcc/files/production/public/2011Foundation/PDFs/2017PHCCScholarshipApplicationForm.pdf

Sunday, February 26, 2017

Slow Times

I believe most of the United States is experiencing unseasonably warm weather right now. Here it is the end of February and friends in Chicago are going to the zoo, people are gardening in New Jersey, and here in Georgia folks are running around in shorts and tees. So, what are you doing with all the spare time? The warm February weather is nice, but it is not very good for business! I have a suggestion for your down time. When you get tired of cleaning up the shop and the truck, how about investing some time into education? Now that you have time, invest some time studying those things that you never have time to get to during a busy season. You can take classes or just do some self-study and research. It is very easy to get information now, so take advantage of your time. Studying during slow times is a great way to prepare for the future.

Saturday, February 18, 2017

Furnace Door Switch

One of the first things most technicians do when troubleshooting a gas furnace is to disable the blower door switch. The blower door switch kills power to the furnace when the blower door is removed. Since the controls and blower are in that compartment, it is impossible to work on the electrical controls with the blower door removed if you do not jump out or physically disable the door switch. Many folks use duct tape to keep the switch closed. Many techs don’t know why the switch is there, and some make their life easier by just removing the door switch altogether. This is a bad idea.

The door switch is there to prevent the blower from sucking in vent gasses and circulating them through the house. The suction created by the blower can be stronger than the draft created in the vent. If the furnace is operating in an enclosed space and with the blower door off, the fan can literally suck vent gasses out of the vent. This can cause two problems. One, the negative room pressure can interfere with the furnace getting enough combustion air, and two, the vent stops working – dumping combustion gasses into the room. This creates a situation where carbon monoxide can be created, dumped into the room, picked up by the blower and circulated through the house. This is especially true for furnaces that get their combustion air from space in where they are installed.

What about sealed combustion systems which draw combustion air from outside through a PVC pipe? Although the combustion air for a sealed combustion furnace normally comes from outside via the PVC combustion air pipe, if you remove the panel to the burner compartment, the furnace will be pulling air from the surrounding area. More to the point, the vent gasses could conceivably be pulled out through the burner area. Although not likely, if both panels are off it is possible for the blower to create a strong enough negative pressure to interfere with the combustion process even with a sealed combustion furnace.

So after working on a gas furnace make sure the door switch is functional before you leave. Do not leave it jumped out or mechanically defeated. You do not want to be responsible for a tragedy.

Friday, February 10, 2017

2017 National HVACR Educators and Trainers Conference

There is still time to register for the HVAC Excellence National HVACR Educators and Trainers Conference is this coming on March 27-29 at the Florida Hotel and Conference Center in Orlando, Florida. I will be speaking at the conference and will be at the Pearson booth at the Expo. Please come by and say hello. I love to talk with other HVACR Instructors. Not an instructor? No problem. Techs and contractors are welcome as well. You can pick up on many of the latest topics. Better yet, you can meet the dedicated people teaching HVACR. You really can’t find this amount of quality continuing education anywhere else for the price of these conferences. Come and fill up at the all you can learn educational buffet being offered.

If you can find a way to attend one of this conference you won’t be disappointed. They are well worth your time. Unlike generic teacher’s conferences that target all subjects, these are specific to our field. And unlike industry showcases like ComforTech or the AHR show, these are specifically for teachers. As a result, everything you see will have a direct application to teaching HVAC/R.

I know that times are tough and getting funding and permission to go is difficult. When presenting the idea to your school administrators be sure to forward a copy of the program from the conference. The sessions at the National Educators and Trainers Conference in Orlando are high quality, professional programs, not sales pitches. The presenters are nationally recognized speakers from respected HVACR organizations. Be sure to note the large number of educational sessions. There are literally more sessions than you will have time to attend. Point out that attending will keep you informed about emerging technology like communicating systems. Point out that by attending you will be better positioned to integrate green mechanical concepts into your curriculum as a result of attending the conferences. Your attendance is tracked, so you can prove the number of hours you attended. Finally, you can get enough free instructional material and tools to help your program. Come gorge yourself at the all you can learn buffet! Here is a link for more information about the conference

Friday, January 27, 2017

ShurTape Mission HVAC

Shurtape Mission HVAC is looking for applicants who are willing to write small blog posts about HVAC in return for $500 per post at 10 posts per year. That is $5000 for researching and writing 10 short blog posts. We have had students participate in this program in the past and they found it very rewarding. Sadly, the Shurtape folks don't want worn out HVACR instructors, or I would be all over that. They want HVACR students. You need to move quickly, the cut-off date is February 3.
You can contact

Laura Pierce
lpierce@shurtape.com
Senior Media Manager
Shurtape Technologies, LLC
1712 8th Street Drive SE
Hickory, NC 28602
P +1-828-267-8506

To see more about the program look here

Saturday, January 21, 2017

Deja Vieux

We have been here before. An outgoing administration is promulgating lots of final rulings in their last gasp and an incoming administration is working hard to undo those rulings. We the regulated, are caught in the middle.

SEER 13 SEER 12 SEER 13
Just before January 20, 2001 when Bill Clinton left office, the Department of Energy upped the minimum SEER from 10 to 13. The change was to take effect in 2006. ARI objected and the Bush administration agreed to drop the minimum from 13 to 12. The DOE published the new 12 SEER standard in May 2002. Several states as well as national environmental and consumer groups successfully sued.  On Jan. 13, 2004, the U.S. Appeals Court for the 2nd Circuit, based in New York, ruled that the DOE did not follow "proper procedures" when it adopted its 12 SEER standard in May 2002. The more stringent 13 SEER standard was reinstated.

This is an oversimplification of the actors and events, but tell the basic story. Instead of having from 2001 until 2006 to reinvent their product line, manufacturers had only from May of 2004 until January of 2006 because of the regulation wars. In retrospect, it would have been far easier to shoot for the 13 SEER target from the beginning and have several more years to accomplish it.

HFC Phasedown
Like a case of deja vieux, the outgoing Obama administration just signed a Global Warming amendment to the Montreal Protocol this past October and the incoming Trump administration wants to scrap all Global Warming initiatives. However, AHRI is not beating the drums to slow down or scrap the HFC reductions. Instead they are saying that what they really want is regulatory consistency and certainty. In other words, they don’t want to relive the 2001 – 2006 SEER wars.

Nothing is Constant but Change
There are mid-term elections in two years, and the ruling party almost always take a beating, meaning the senate may change hands in two years. If this election has taught us anything, it is that we cannot know for certain who will be heading up the government in four years. In eight years we are guaranteed to have a change at the top. It takes years to develop and test new products, and the last thing any manufacturer wants is to have the design parameters altered drastically and capriciously based on the latest election. Even if the challenges are steep, they can be met with a reasonable time for development if you don’t keep moving the goal posts.

To read more about the history of the SEER wars read this excellent article in the NEWS.
http://www.achrnews.com/articles/97373-how-we-got-to-13-seer

To read more about AHRIs position on the HFC phasedown, read this NEWS article
http://www.achrnews.com/articles/134252-kigali-agreement-creates-orderly-phasedown-of-hfcs